Connecting the converter to the line supply

Connect the line supply as shown in the following to connector X1 of the converter. Connect the
protective conductor with a cable lug and an M4 screw to the shield plate of the converter.
If you do not use a shield plate, then you must connect the protective conductor directly at the
device.
The terminals are spring-loaded terminals.
Figure 5-14
Permissible conductor cross-sections for single-conductor connection or for connecting flexible
cables with end sleeves:
● 0.2 mm
● AWG: 26 ... 12
SINAMICS S210 servo drive system
Operating Instructions, 01/2019, A5E41702836B AC
X1 - line connection 1 AC
... 2.5 mm2
2
2
5.4 Connecting the converter and the motor
Installing