Automatic Operation (Position Control)
8.9.2 Procedure of Rewriting Positioning Data
The following flowchart shows the flow of the operation required in a user program.
• For reading and writing, the operations to be executed (read, write) and targets (axis number,
table number, table size) are specified in the buffer control area of the unit memories.
• By executing "Recalculation" after the operation, the positioning data stored in the system
area of FP7 MC Unit is updated. Once the "Recalculation" is completed, the positioning
operation can be started for the rewritten positioning data.
Axis no. / Table control setting
Select target
Setting value
partial change
Read
Buffer control read request
Set
Parameter partial change
Write
Buffer control write request
Recalculation table specification
Starting number and size
Recalculate
Recalculation request : Y7=ON
Recalculation done: X7=ON
8-48
START
No
Yes
Request code: H0080
Request flag: H0001
Request code: H0081
Request flag: H0001
END
All parameter settings