CMTimeChart Monitor
 Unit memories (Time chart function operation setting/annunciation area)
Unit
Axis
memory
Name
no.
no. (Hex)
Announce trigger
-
UM 02630
registration
-
UM 02631
Allow trigger use
-
UM 02632
Logging flag
Presence/absence
-
UM 02633
of logging data
(Note 1): Sixteen bits corresponding to respective trigger numbers are allocated to the time chart function operation
setting/annunciation area (1 word).
bit no. 15
● ● ● ● ● ●
Trigger no.
16
14-16
Default Description
When a trigger condition has been registered in FP7
MC Unit, the bit corresponding to the trigger number
turns on.
H0
0:Not registered
1: Trigger condition is registered.
For allowing the use of a trigger by a user program,
turn the bit corresponding to the trigger number.
H0
0:Not allow the use.
1: Allow the use.
It turns on when the logging operation is being
executed on FP7 MC Unit. It turns off when the
logging operation is complete.
H0
0:Logging is not executed / complete.
1: During logging
It turns on when the logging operation is complete
on FP7 MC Unit and logging data exists.
H0
0:No logging data
1: Logging data exists.
8 7
0
● ● ● ● ● ●
9
8
1
●: Available, -: Not available