HEIDENHAIN iTNC 530 Service Manual page 188

Hide thumbs Also See for iTNC 530:
Table of Contents

Advertisement

Transferring data
from the USB flash
drive
13 – 188
Caution
Use thedual-window conceptalso on the iTNC 530 processor control with Windows
when transferring control data from a USB stick to the control.
Only then the required ASCII-to-BINARY data conversion is ensured.
Note
To change to the PLC partition you must have entered the PLC code number before.
Note
The following description uses the program manager with the setting Enhanced 1 --> See
"Setting the Program Manager" on page 12 – 162.
Switch to the Programming and Editing operating mode (for TNC data) or
PLC programming (for PLC data) and press the PGMMGT key.
Place the cursor on the USB0:\ directory
(or on the subdirectory from which you wish to take the data).
Press the WINDOW soft key (switch to next soft-key row). --> The display changes to the
dual-window concept:
Place the cursor in the right half on the directory or subdirectory to which you wish to transfer
the data.
Note
Press the soft keys PATH and FILES to activate the respective view.
Return to the other side now.
HEIDENHAIN Service Manual iTNC 530