Dead Zone Generation - Wiznet W7500 Reference Manual

W7500 series
Hide thumbs Also See for W7500:
Table of Contents

Advertisement

If interrupt occurs, corresponded bit of Channel-x interrupt register(CHn_IR) bit is set and
PWM channel-n interrupt signal is generated. All CHn_IR is cleared by channel-n interrupt clear
register(CHn_ICR) and then PWM channel-n interrupt signal is cleared.

Dead zone generation

Each PWM channel can output two complementary signals with dead zone time and it can be
enabled by Channel-n Dead Zone Enable Register(CHn_DZER). Only 4 channels can be enabled
because there are 8 PWM output pins. Channel 0 and 1 are a pair, channel 2 and 3 are a pair,
channel 4 and 5 are a pair, and channel 6 and 7 are a pair. If users want to use channel-0 dead
zone generation, channel-1 should be disabled. If channel 0 and 1 dead zone generation are
enabled both, all outputs are 0. In that case, users should choose 1 channel.
Dead zone time are generated by the value of Channel-n Dead Zone Counter Register(DZCR).
The dead zone counter counts up to value of DZCR. During the dead zone time, both
complementary signals are both 0. Users have to adjust the signal depending on the devices
that are connected to the outputs and their characteristics. If DZCR is bigger than the limit
register, main output signal is toggled 0 to1 and then 1 to 0 while 1 PWMCLK and inverted
output signal is always 0.
Figure 34 shows two complementary PWM outputs with dead zone time. During dead zone time,
both outputs are 0. Figure 35 shows a more detailed timing with dead zone counter. The dead
zone counter and the Timer/Counter starts to count together and PWM output is 0 until dead
zone counter is reached to value of dead zone counter register. The PWM output becomes 1
and 0 when the Timer/Counter is reached to value of match register. The inverted PWM output
is also 0 until dead zone counter is reached to value of dead zone counter register. Then
inverted PWM output becomes 1 after dead zone counter is reached to the value of dead zone
counter register.
PWM
output
Inverted PWM
output
Dead zone
time
W7500x Reference Manual Version1.1.0
Dead zone
time
Figure 34 PWM waveform with dead zone time
Dead zone
Dead zone
time
time
Dead zone
time
195 / 399

Advertisement

Table of Contents
loading

This manual is also suitable for:

W7500p

Table of Contents