15 TROUBLESHOOTING
LED indicator
Classifica
of servo
Error
tion of
amplifier
code
errors
IFU
2033
FA.33
Servo
amplifier
errors
2034
FA.34
2035
2036
FA.36
2037
FA.37
Error name
DRU
Converter bus voltage
Overvoltage
exceeded 400VDC.
SSCNET cable communication
CRC error
fault
Command
@A.35#
pulse
Input frequency of too high.
frequency error
SSCNET cable or printed board
Transfer error
is faulty.
IFU parameter
IFU parameter setting is wrong. There is a IFU parameter whose
error
Description
15 - 82
MELSEC-Q
Cause
Don't using the regenerative brake
option.
Though the regenerative brake
option is used, the DRU parameter
" Pr.102 Regenerative brake
resistor "setting value is "0 00 (not
used)".
Regenerative brake option is open
or disconnected.
Regenerative transistor faulty.
Wire breakage of built-in
regenerative brake resistor or
regenerative brake option
Power supply voltage high.
The SSCNET cable is
disconnected.
The SSCNE cable fault.
Noise has entered the SSCNE
cable.
The terminal connector is
disconnected.
The same No. exists in the interface
unit side axis setting.
Command given is greater than the
maximum speed of the servomotor.
Noise has entered the SSCNET
cable.
Fault in the QD75M.
The SSCNET cable is
disconnected.
The SSCNET cable fault.
Printed circuit board fault.
The terminal connector is
disconnected.
Interface unit fault caused the IFU
parameter setting to be rewritten.
value was set to outside the setting
range by QD75M.