Mitsubishi Electric MELSEC-Q QD75M User Manual page 469

Positioning module
Table of Contents

Advertisement

9 MAJOR POSITIONING CONTROL
[2] Changing to a new current value using the start No. (No. 9003) for
a current value changing
Operation chart
The current value is changed by setting the new current value in the current value
changing buffer memory "
"
Cd.3
Positioning start No.", and turning ON the positioning start signal.
Positioning start signal
[Y10,Y11,Y12,Y13]
Md.20 Current feed value
Restrictions
(1) An axis error "Outside new current value range (error code: 514)" will occur if
the designated value is outside the setting range when "degree" is set in "Unit
setting".
(2) An error "Software stroke limit +,
designated value is outside the software stroke limit range.
(3) The current value cannot be changed during stop commands and while the M
code ON signal is ON.
(4) The M code output function is made invalid.
Current value changing procedure
The following shows the procedure for changing the current value to a new value.
1)
Write the current value to " Cd. 9 Current value changing"
Write "9003" in " Cd. 3 Positioning start No."
2)
Turn ON the positioning start signal.
3)
Cd.9
Current value changing", setting "9003" in the
ON
OFF
50000
0
Current value changes to the
positioning address designated by
the current value changing buffer memory.
The above chart shows an example
when the positioning address is "0".
(error code: 507 or 508)" will occur if the
9 - 108
MELSEC-Q