Mitsubishi Electric MELSEC-Q QD75M User Manual page 125

Positioning module
Table of Contents

Advertisement

5 DATA USED FOR POSITIONING CONTROL
Pr.21 Current feed value during speed control
Specify whether you wish to enable or disable the update of "
value" while operations are performed under the speed control (including the
speed-position and position-speed switching control).
0: The update of the current feed value is disabled
1: The update of the current feed value is enabled
2: The current feed value is cleared to zero
Note1: When the speed control is performed over two to four axes, the choice
between enabling and disabling the update of "
depends on how the reference axis is set.
Note2: Set "1" to exercise speed-position switching control (ABS mode).
Pr.22 Input signal logic selection
Set the input signal logic that matches the signaling specification of the connected
external device.
Negative logic
(1) When the input signal contact is not flowed with the current.
(a) FLS, RLS
(b) DOG, STOP, CHG
(2) When the input signal contact is flowed with the current.
(a) FLS, RLS
(b) DOG, STOP, CHG
Positive logic
Opposite the concept of negative logic.
Note1: A mismatch in the signal logic will disable normal operation. Be careful of
this when you change from the default value.
Note2: Set the manual pulse generator input logic selection (b8) to axis 1. (Setting
of any of axes 2 to 4 is invalid.)
The current feed value will not change.
(The value at the beginning of the speed control
will be kept.)
The current feed value will be updated.
(The current feed value will change from the
initial.)
The current feed will be set initially to zero and
change from zero while the speed control is in
effect.
: ON (Limit signal turn ON)
OFF
OFF (Limit signal turn OFF)
ON
5 - 34
MELSEC-Q
Md.20
Current feed
Md.20
Current feed value"