15 TROUBLESHOOTING
Related buffer memory
address
Axis 1 Axis 2 Axis 3 Axis 4
ABS setting direction in the
unit of degree
1550 1650 1750 1850
Software stroke limit
upper limit
18
168
318
468
19
169
319
469
Software stroke limit
lower limit
20
170
320
470
21
171
321
471
1901
Set range
(Setting with PLC program)
0: Shortcut
1: Clockwise
2: Counterclockwise
• [mm] [inch] [PLS]
–2147483648 to 2147483647
• [degree]
0 to 35999999
<Parameter initialization request>
1: Parameter initialization is
requested
<ABRST status>
0: Communication complete
(received from the servo amplifier)
<PSTRT start No.>
1 to 600, 7000 to 7004, 9001 to 9004
<TEACH teaching data selection>
0: The current feed value is written to
the positioning address.
1: The current feed value is written to
the arc address.
<TEACH positioning data No.>
1 to 600
• Set the ABS setting direction in the unit of degree
within the setting range.
• Set "0" when the software stroke limits are valid.
(Refer to Section 9.1.5)
Invalidate the software stroke limit.
(To invalidate, set the software stroke limit upper limit
value to the software stroke limit lower limit value.)
(Refer to Section 9.1.5)
Clear the setting of the PLC CPU module parameter
"Output at error stop".
(Refer to "QCPU User's Manual")
Replace the flash ROM with a new one.
Return the parameter to that set at the time of delivery
from the plant. (Refer to Section 13.2)
(Refer to "QCPU User's Manual")
• When executing the ABRST instruction, set the
status to 0 (refer to Section 14.3).
• When executing the PSTRT instruction, set the start
No. to within the setting range (refer to Section 14.4).
• When executing the TEACH instruction, set the
teaching data selection and positioning data No. to
within the setting range (refer to Section 14.5).
• Do not specify the instruction of a non-existent axis by
the ABRST , PSTRT and TEACH instructions
(refer to Section 14.3 to Section 14.5).
Review the PLC program so that data is not written
continuously to the flash ROM. (Using "
Section 5.6.1, the number of flash ROM write times can
be monitored.)
(If this error has occurred in a proper using method,
writing is enabled by resetting the error, switching
power OFF, then ON, or resetting the PLC CPU.)
15 - 23
MELSEC-Q
Remedy
" in
Md.19