15 TROUBLESHOOTING
LED
Classifica
Error
indicator
tion of
code
of servo
errors
amplifier
2033
33
2034
34
Servo
amplifier
errors
2035
35
2036
36
2037
37
2046
46
Error name
Converter bus voltage exceeded
Overvoltage
400VDC.
CRC error
SSCNET cable communication fault
Command pulse
Input frequency of too high.
frequency error
SSCNET cable or printed board is
Transfer error
faulty.
Parameter error Parameter setting is wrong.
Servomotor
Servo motor temperature rise
heated
actuated the thermal protector.
Description
15 - 50
MELSEC-Q
Cause
Lead of built-in regenerative brake
resistor or regenerative brake option
is open or disconnected.
Though the regenerative brake
option is used, the DRU parameter
" Pr.102 Regenerative brake
resistor "setting value is "0 00 (not
used)".
Regenerative brake option is open
or disconnected.
Regenerative transistor faulty.
Wire breakage of built-in
regenerative brake resistor or
regenerative brake option
Capacity of built-in regenerative
brake resistor or regenerative brake
option is insufficient.
Power supply voltage high.
The SSCNET cable is
disconnected.
SSCNET cable fault.
Noise has entered the SSCNET
cable.
The terminal connector is
disconnected.
The same No. exists in the servo
amplifier side axis setting.
Command given is greater than the
maximum speed of the servomotor.
Noise has entered the SSCNET
cable.
Fault in the QD75M.
The SSCNET cable is
disconnected.
The SSCNET cable fault.
Printed circuit board fault.
The terminal connector is
disconnected.
Servo amplifier fault caused the
parameter setting to be rewritten.
Parameter data mis-setting by
QD75M.
Servo motor ambient temperature
exceeded the operating value of
40°C.
Servomotor overloaded.
Thermal protector in encoder is
faulty.