Mitsubishi Electric MELSEC-Q QD75M User Manual page 428

Positioning module
Table of Contents

Advertisement

9 MAJOR POSITIONING CONTROL
Setting item
Da.1 Operation pattern
Da.2 Control system
Da.3 Acceleration time No.
Deceleration time
Da.4
No.
Axis to be
Da.5
interpolated
Positioning address/
Da.6
movement amount
Da.7 Arc address
Da.8 Command speed
Da.9 Dwell time
Da.10
M code
Refer to Section 5.3 "List of positioning data" for information on the setting details.
Positioning data setting examples
[Reference axis and interpolation axis are designated as axis 1 and axis 2,
respectively.]
The following table shows setting examples when "2-axis circular interpolation
control with center point designation (INC circular right, INC circular left)" is set in
positioning data No. 1 of axis 1. (The required values are also set in positioning
data No. 1 of axis 2.)
Axis 1
Axis 2
Axis
(reference
(interpolation
axis) setting
axis) setting
example
example
Positioning
complete
INC circular
right
INC circular
left
1
0
2
8000.0 µ m
6000.0 µ m
4000.0 µ m
3000.0 µ m
6000.00
mm/min
500ms
10
POINT
Set a value in "
Da.8
Command speed" so that the speed of each axis does not
Pr.8
exceed the "
Speed limit value". (The speed limit does not function for the
speed calculated by the QD75 during interpolation control.)
Set "Positioning complete" assuming the next positioning
data will not be executed.
Set incremental system, 2-axis circular interpolation control
with center point designation. (Select clockwise or
counterclockwise according to the control.)
Designate the value set in " Pr.25
as the acceleration time at start.
Designate the value set in " Pr.10
as the deceleration time at deceleration.
Set the axis to be interpolated (partner axis).
If the self-axis is set, an error will occur.
Set the movement amount. (Assuming that the " Pr.1
Unit setting" is set to "mm".)
Set the center point address. (Assuming that the " Pr.1
Unit setting" is set to "mm".)
Set the speed when moving to the end point address.
(Designate the composite speed in " Pr.20
speed designation method".)
Set the time the machine dwells after the positioning stop
(pulse output stop) to the output of the positioning complete
signal.
Set this when other sub operation commands are issued in
combination with the No. 1 positioning data.
9 - 67
MELSEC-Q
Setting details
Acceleration time 1"
Deceleration time 0"
Interpolation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents