Recommended Programming; Enhanced Communication Parameters - Bosch B9512G Installation Manual

Hide thumbs Also See for B9512G:
Table of Contents

Advertisement

32
en | ULC Installation Guide
Figure 1.24: Enhanced Communication parameters
1.5.2

Recommended programming

AREA WIDE PARAMETERS > Area Name Text > Area 1
For ease of identification, name the AREA WIDE PARAMETERS >
Area Name Text > Area 1 parameter FIRE AREA.
Control panel silencing of fire alarm panel alarm, trouble, and
supervisory events
When control panels are configured as described below, they
automatically silence keypads connected to the control panel for
fire, trouble, and supervisory events from the fire panel.
Notice!
Automatic silence not available for B3512 control panels
Automatic silencing of fire alarm panel alarm, trouble, and
supervisory events is not available for the B3512 control panel.
Users must silence these events at the keypad.
CUSTOM FUNCTIONS > Custom Function 128
Set Custom Function 128 > Custom Function Text to: Silence.
Set Custom Function 128 > Function 1 to: Trouble Silence (set
Parameter 1 to: Area 1).
Set Custom Function 128 > Function 2 to: Alarm Silence (set
Parameter 1 to: Area 1).
2019.06 | 02 | F.01U.321.698
Control Panels
Bosch Security Systems B.V.