Characteristics Of A Fire Point - Bosch D9412GV4 Program Entry Manual

Table of Contents

Advertisement

D9412GV4/D7412GV4/D7212GV4
Combining Point Response 9 with the Local While Armed feature provides off-site reporting
when the area is disarmed, but only local alarm annunciation when the area is armed.
Point Response E: Use this setting for Zonex or ASIC motion detectors. The control panel can
report troubles while Master Armed.
Point Response F: Does not sound at local keypads but activates a relay when P## Relay
Response Type is set to 1 and annunciates a fault at the keypads. To annunciate the off-
normal state at a keypad, program P## Display as Device as Yes or optionally set P## BuzzOn
Fault as 1 or 2. This point response does not generate alarms nor does it activate the Alarm
Bell.
Point Response 8, 9, A, B, and C: These point responses provide supervisory (24-hour)
reporting.
5.2.2

Characteristics of a Fire Point:

Reporting: When a group of events occurs, the control panel routes and prints out Fire
Reports first.
Visual Annunciation: FIRE TROUBLES continues to scroll until the trouble clears. When
acknowledged, a FIRE TROUBLE scroll notifies the end user that a Fire point, or group of Fire
points, is still in trouble. Panel-Wide Relays, Summary Fire, and Summary Fire Trouble
activate if a relay is assigned when any Fire point enters into alarm or is in trouble.
Audible Annunciation: A Fire point activates the A# Fire Bell relay programmed in Relay
Parameters. The amount of time and the pattern of the relay activation is programmed by area
in Bell Parameters, A# Fire Time, and A# Fire Pattern.
Supervisory: A Fire point can send a Fire Supervisory Report and activate the Summary Fire
Sup and Summary Fire Trouble, Panel-Wide Relays with a P## Response of 8-9-A-B-C.
Alarm Verification: A Fire point can delay an alarm by the length of time programmed in A#
Verify Time in the Area Parameters. Combined with A# Resettable, a Fire point also resets
the electrical circuit for the amount of time programmed.
Reset Sensor: A fire device that requires resetting can be manually reset using the reset
sensor relay for the area to which it is assigned.
Fire Walk: Use the Fire Walk function to test Fire points in the system. The Fire Walk Test
automatically resets each point for 5 sec when the point is activated, and rings the Fire Bell
for 2 sec.
NOTICE!
To provide remote annunciation for a restored Fire Supervisory point, use P## Relay
Response Type set to 1 and connect the corresponding relay to an annunciator.
Bosch Security Systems, Inc.
Program Entry Guide
Points | en 133
F.01U.218.312 | 04 | 2012.03