Log % Full; Summary Fire; Summary Alarm; Summary Fire Tbl - Bosch D9112B Program Entry Manual

Control panel
Table of Contents

Advertisement

D9112B | Program Entry Guide | 10.0 Skeds

Log % Full

Default:
Blank
Selection:
Blank, 1 to 128, A, B, or C
Enter the number of the relay that activates when
the log has reached the programmed percentage of
its capacity as programmed in RAM Parameters
Log % Full
program item
steady output until a "vacuum log" is performed
from the RAM, or the panel is reset.

Summary Fire

Default:
Blank
Selection:
Blank, 1 to 128, A, B, or C
Enter the number of the relay that activates when a
fire point goes into alarm. This relay provides a
steady output until the alarm is cleared from alarm
memory at the command center.

Summary Alarm

Default:
Blank
Selection:
Blank, 1 to 128, A, B, or C
Enter the number of the relay that activates when a
controlled point goes into alarm. This relay provides
a steady output until the alarm is cleared from alarm
memory at the command center.

Summary Fire Tbl

Default:
Blank
Selection:
Blank, 1 to 128, A, B, or C
Activates when any fire point in the panel is in
trouble. This relay provides a steady output until the
trouble is cleared from alarm memory at the
command center.

Summary Trouble

Default:
Blank
Selection:
Blank, 1 to 128, A, B, or C
Activates when any on-fire point in the panel is in
trouble. This relay provides a steady output until the
trouble is cleared from alarm memory at the
command center.
Bosch Security Systems | 2/04 | 74-06145-000-D
. This relay provides a

10.0 Skeds

Use the Skeds module to program the D9112 to
automatically execute functions on a specific date or
day of the week. You can program up to seventeen
Skeds in the D9112.
Each Sked can be programmed with one of fifteen
functions. Some functions codes require that you
enter additional parameters. The functions and their
associated parameters are listed in the "Sked
Function Code Table" in the Program Record Sheet,
and they are explained in detail following the
Function Code
prompt.
Each Sked can be programmed with up to four
Holiday Indexes. The Holiday Indexes can be used
to execute the Sked on the holidays in the addition
to the Date or Day(s) of the week, or they can be
used to prevent the Sked from executing on the
S## Xept Holiday
holidays (see

Sked Number

Default:
1
Selection:
1 to 17
Enter the number of the Sked you are programming.
EN | 86
S##
).