Connecting an MX960 Router to an External Alarm-Reporting Device
Copyright © 2017, Juniper Networks, Inc.
NOTE:
For console devices, configure the serial port to the following values:
Baud rate—9600
Parity—N
Data bits—8
Stop bits—1
Flow control—none
Figure 79: Auxiliary and Console Ports
Figure 80: Routing Engine Console and Auxiliary Cable Connector
To connect the router to external alarm-reporting devices, attach wires to the
relay contacts on the craft interface. (See
YELLOW
condition that triggers the red or yellow alarm LED on the craft interface also activates
the corresponding alarm relay contact.
The terminal blocks that plug into the alarm relay contacts are supplied with the router.
They accept wire of any gauge between 28-AWG and 14-AWG (0.08 and 2.08 mm
which is not provided. Use the gauge of wire appropriate for the external device you are
connecting.
To connect an external device to an alarm relay contact (see
Prepare the required length of wire with gauge between 28-AWG and 14-AWG (0.08
1.
2
and 2.08 mm
).
While the terminal block is not plugged into the relay contact, use a 2.5-mm flat-blade
2.
screwdriver to loosen the small screws on its side. With the small screws on its side
facing left, insert wires into the slots in the front of the block based on the wiring for
the external device. Tighten the screws to secure the wire.
Chapter 18: Connecting the MX960 Router to the Network
Figure 81 on page
Figure 81 on page
and
RED
250.) A system
2
),
250):
249