Pilot-Wire Data With Bridgeable Distance For The Cc-Co - Siemens 7XV5662-0AC02 Manual

Communication converter - copper/synchronous interface
Hide thumbs Also See for 7XV5662-0AC02:
Table of Contents

Advertisement

Available languages

Available languages

Technical Data

6.3 Pilot-Wire Data with Bridgeable Distance for the CC-CO

6.3

Pilot-Wire Data with Bridgeable Distance for the CC-CO

Reference Values
AWG
19
20
21
8
22
23
24
25
26
27
28
NOTE
i
i
The loop impedance is considered when specifying the reference values. Furthermore, the bridgeable
distances depend on the type and structure of the cable.
Resistance for the converter modulation frequency
7
8
Data for a twisted pair of telephone wires
38
Diameter (mm) Cross-Section
(mm
2
)
0.91
0.65
0.81
0.52
0.72
0.41
0.64
0.32
0.57
0.26
0.51
0.20
0.45
0.16
0.41
0.13
0.36
0.10
0.32
0.08
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
Line Impedance
Ω/km (50/60 Hz) Ω/km (80 kHz)
27.37
57.74
34.54
66.17
43.72
76.18
55.33
88.01
69.76
101.86
87.13
117.73
111.92
139.47
134.82
159.04
174.87
192.88
221.32
232.45
C53000-B1174-C190-1, Edition 01.2022
Max.
distance CC
7
↔ CC (km)
12.1
10.6
9.2
8.0
6.9
5.9
5.0
4.4
3.6