3

3.3 SAFETY STOP FUNCTION

The inverters CFW11...O...Y... have the board SRBXX that implements Safety Stop function. Through this board it
is possible to control two safety relays (K1 and K2) that actuate directly on the power circuit, more specifically on
the IGBTs gate drivers power supply. The basic functional block diagram is shown in
The safety relays guarantee that the IGBTs remain switched off when Safety Stop function is activated, even in
case of an internal single failure. The position of SRBXX board and XC25 terminals (Safety Stop control terminals)
on the inverter is shown in
The Safety Stop function prevents the motor starting accidentally.
3-54 | CFW-11
Stop/Forward S1
Stop/Reverse S2
Figure 3.44 - XC1 wiring for control connection # 4
Figure 3.38 on page
3-49.
XC1 Terminal Strip
1
+ REF
2
AI1+
3
AI1-
4
- REF
5
AI2+
6
AI2-
7
AO1
8
AGND (24 V)
9
AO2
10
AGND (24 V)
11
DGND *
12
COM
13
24 Vdc
14
COM
15
DI1
16
DI2
17
DI3
18
DI4
19
DI5
20
DI6
21
NC1
DO1
22
C1
(RL1)
23
NO1
24
NC2
DO2
25
C2
(RL2)
26
NO2
27
NC3
DO3
28
C3
(RL3)
29
NO3
Figure 3.45 on page
3-55.