Calendar Set - Eaton i-on series Engineering Manual

Hide thumbs Also See for i-on series:
Table of Contents

Advertisement

i-on Range
If you wish to link/unlink partition 1 to many partitions then you can use the "All Partitions"
option (in between partition 2 and the last partition on the menu on the menu) to either link
or unlink partition 1 to all the other partitions in one operation. Once you have carried out
this operation you can then scroll through the partition list and change the linking as
necessary.

Calendar Set

50 160
Using the calendar set option you can program the control unit to set or unset the alarm
system (or parts of it) at fixed times of day on a seven day cycle. If the system is set up as
a part setting system then you can use this option to Full Set or Part Set-B, -C or -D. If the
system is set up as a Partitioned system then this option allows you to Full Set or Part Set
any collection of partitions.
There are two basic elements that you can program within the calendar set option: the
"event" and the "exception".
Each event specifies:
A 12 character name as a reminder of the purpose of the event.
A time on the 24 hour clock
One or more days of the week
An action (setting, part setting or unsetting).
Optionally, one or more exceptions.
A warning time, during which a warning tone can sound before the system sets.
A warning tone, which the system can give during the warning time.
Each exception marks a time period when certain events do not apply. An exception has a
start time and date, an end time and date, and a name. You link events to exceptions while
programming events – see below.
The i-on160EX can store up to 20 events and 30 exceptions. The i-on50EX can store up to
five events and 30 exceptions.
By using events and exceptions you can program the system to set in a regular pattern for
each day of the week, except during significant holidays (or other events) that occur at
known times during the year.
Hint: When you are programming calendar set options it is advisable to set up your
exceptions first, and then add the events.
Please Note: The control unit adjusts its clock in Spring and Autumn to allow for Summer
Daylight Saving Time. At the Autumn change-over avoid programming any unset
events to take place during the changeover time on the Sunday morning. For UK
systems this time is 01:00 to 02:00. For EUR systems this time is 02:00 to 03:00. If
the control unit does unset any part of the system at these times then it will NOT set
the system again when the clock changes back to Winter Time.
Calendar Set Options
Add Event
Use this option to create an event. When you select the option the control unit will
guide you through the following series of steps to ensure that you add all the required
information:
Event Name. Key in a 12 character name (or press  to leave the default name).
Event Time. Use the 24 hour clock. Note that if you specify a start time that is less
than 10 minutes from the current time shown by the control unit clock (less than the
Installer Menu Options
Page 83

Advertisement

Table of Contents
loading

Table of Contents