Zone Programming; Partition And Other Programming - Eaton i-on series Engineering Manual

Hide thumbs Also See for i-on series:
Table of Contents

Advertisement

i-on Range
area (P1) follow the status of other partitions use the Partitions - Full Set Link option (see
below).
To avoid false alarms make the alarm response of the common area (Partition 1) Siren +
Comms and the other two Partitions Siren only.

Zone Programming

Location
Front Door
Foyer PIR
Loading Bay Entrance
Roller shutter
Loading Bay PIR
Factory PIR
Factory Fire Door
Kitchen PIR
Office Fire Door
Office PIR
Reception PIR
Reception Entrance

Partition and Other Programming

Menu
Add/delete
Wired keypads
Outputs
Partitions
Zone
Name
001
Front Door
002
Foyer PIR
003
LB to Foyer
004
Rshutter
005
LBay PIR
006
Factory PIR
007
Factory FD
008
Kitchen PIR
009
Office FD
010
Office PIR
011
Recpt PIR
012
Rcept Door
Sub Menu
Detectors/Devices
Keypad 01
Keypad 2
Keypads 3 & 4 – not
fitted
Panel Outputs
P1
P2
P3
Full Set Link
Zone Type
Final Exit
Entry Route
Final Exit
Normal Alarm
Entry Route
Normal Alarm
24 Hour
Normal Alarm
24 Hour
Normal Alarm
Entry Route
Final Exit
Option
External Radio Siren (if to be fitted)
Name = Office
Partition 3
Name = Factory
Partition 2
NA
1 = Siren
2 = Strobe
3 & 4 = NU
Name = Foyer
Exit Mode = Final Door Set
Settle Time = 10s
Entry Time = 45s
Alarm Response = Siren + Comms (Full)
Strobe on Set = Yes (If required)
Strobe on Unset = Yes (if required)
Name = Offices
Exit Mode = Timed
Exit Time = 20s
Entry Time = 45s
Alarm Response = Siren (Local)
Name = Factory
Exit Mode = Timed
Exit Time = 20s
Entry Time = 45s
Alarm Response = Siren (Local)
P2 = Yes
Appendix II
Partitions
P1
P1
P2
P2
P2
P2
P2
P1
P3
P3
P3
P3
Page 141