i-on Range
In a Part Setting system the keyswitch can Full Set or unset.
In a Partitioned system you can allocate the keyswitch to one or more partitions.
Each time a user operates the keyswitch the control unit changes the current set
state.
Key Switch Latched – KSL (09)
Use this zone type to connect a fixed position keyswitch to a single zone.
In a Part Setting system the keyswitch can Full Set or unset. As with Momentary
keyswitches, you can allocate the zone to one or more Partitions (see above).
When the user opens the keyswitch contacts then the control unit sets the allocated
Partition. When the user closes the contacts then the control unit unsets the allocated
Partition.
Notes:
1. The keyswitch zone types are intended for use on zones that connect to an
access control keypad, electronic key or other type of hardwired device used to set
or unset the system.
2. When the user operates the keyswitch while the system is unset then the control
unit starts the programmed exit mode.
3. When the user operates the keyswitch while the system is set then the control unit
unsets the system immediately.
4. The user cannot reset the system from a Keyswitch zone.
5. Do not assign more than one Latched Key Switch zone to a partition.
Tamper – T (10)
Use this zone type to monitor the tamper status of external equipment. The control
unit monitors a Tamper zone at all times. When triggered in the unset condition, only
internal sounders operate. When triggered in the set condition, the alarm response
determines whether external sounders, strobe and communications also respond to
the alarm.
External PSU A/C Fail – PAC (11)
Use this zone type to monitor the A/C Fail output of an external power supply unit. If
a power supply unit triggers a zone with this type then the control unit treats this in a
similar way to a mains fail at the control unit itself. The action taken depends on the
values programmed into System Options – Mains Fail Delay (see page 103).
This zone type is not available for radio zones.
External PSU Battery Fault - PBF (12)
Use this zone type to monitor the Battery Fault output of an external power supply
unit. If an external PSU triggers a zone with this type then the control unit activates
any output programmed as "Battery Fault" and causes an alert that displays "External
Battery Fault" on the keypad.
If the alarm system is set then the control unit logs the event, starts any programmed
communication, but does not start an alert until the system is unset.
This zone type is not available for radio zones.
External PSU Low Volts – PLV (13)
Use this zone type to monitor the Low Voltage output of an external power supply
unit. If a power supply triggers a zone with this type then the control unit activates
any output programmed as "Low Volts" and causes an alert that displays "External
Low Volts" on the keypad.
If the alarm system is set then the control unit logs the event, starts any programmed
communication, but does not start an alert until the system is unset.
30 40 50 160.
30 40 50 160
30 40 50 160
30 40 50 160
Installer Menu Options