Extended Sia3 V2 - Eaton i-on series Engineering Manual

Hide thumbs Also See for i-on series:
Table of Contents

Advertisement

i-on Range
Where:
AAAAAA
6-digit programmable account code (e.g. 123456).
"N"
New Event (always N).
"ti"hh:mm/
time (e.g. ti10:23/).
"id"nnn/
user number, if applicable; otherwise not sent (e.g.
id123/ or id6/).
"ri"nn/
partition no. (e.g. ri12/ or ri3).
CC
event code (e.g. FA = Fire Alarm).
cc
zone number, if applicable; otherwise not sent
(e.g. 23 or 5).
"A"S
text description of event, usually the log event
description.
(The control unit sends those characters shown between " and " above literally as they
appear in the text.)
For example, if there is a fire alarm on zone 2 of partition 4 at 10:15 (partition 4 account
number is 10), the message would be:
SIA1:
SIA2:
SIA3:
Extended SIA3:

Extended SIA3 V2

Some versions of the software that works in SIA receivers do not always recognise the "/"
text delimiter. This can cause problems with spurious "Mains Fail" messages appearing to
the ARC when the control unit sets, unsets or goes into or out or installer mode.
In version 2 of Extended SIA3 the "/" delimiter has been replaced by a "|". So, for example,
the string:
#000010|Nti10:15/ri4/FA2/AFire Zone 2
becomes:
#000010|Nti10:15|ri4|FA2|AFire Zone 2
If you have experienced problems with spurious "Mains Fail" messages try using this
Extended SIA3 V2 option.
#000010|NFA2
#000010|N/ri4/FA2
#000010|Nti10:15/ri4/FA2 #000010|AFire Zone 2
#000010|Nti10:15/ri4/FA2/AFire Zone 2