i-on Range
Chime
When enabled by the user, the system gives a non-alarm warning tone when any
zones programmed as 'Chime' are operated. This facility operates only while the
system is unset.
The following zone types can use this attribute: Normal Alarm, Final Exit, Entry
Route, Technical, Log Only and Exit Terminate.
Soak Test
30 40 50 160
Use this zone attribute if you want to place under long term test a detector that you
suspect is giving false alarms. Zones with this attribute are disabled for 14 days after
you return the control unit to user/unset mode. If the zone remains inactive for the
whole fourteen days then after midnight on the 14th day the control unit returns the
zone to normal use.
If the zone is activated during those 14 days while the system is set then the control
unit logs the event as a "Soak Fail Znnn Alm" (nnn is the zone number, see page 25)
without sounding any sirens or starting communications. The control unit also lights
the red LEDs around the navigation key on the keypad to alert the user when they
unset the system. An installer must key in their access code to reset the alert.
During setting the keypad displays a brief message to inform the user that one or
more zones are in soak test.
You can use this attribute on the following zones types: Normal Alarm, Entry Route
and Tamper.
Note: If there is an output configured as "zone follow" for a zone under Soak Test then the
control unit will continue to operate the output if the soak test zone is triggered. The
output will operate whether the zone is set or unset.
Double Knock
30 40 50 160. Not available for radio zones.
Zones programmed with this attribute will cause an alarm only if the zone is EITHER
triggered, restored and triggered again within a five minute period, OR if the zone
remains active for 10 seconds.
You can apply the Double Knock attribute to the Normal Alarm and, Entry Route
zone types.
Note: Double Knock does not comply with EN50131.
Part Set B
(Not visible in a partitioned system.) When a user presses button B (part set), the
control unit sets only those zones where the Part Set B attribute = "Yes". (See also
"Part Set Exit Mode" on page 77 ).
You can apply this attribute to the following zone types: Normal Alarm, Final Exit and
Entry Route.
Part Set C
(Not visible in a partitioned system.) When a user presses button C the control unit
sets only those zones where Part Set C attribute = "Yes".
You can apply this attribute to the following zone types: Normal Alarm, Final Exit and
Entry Route.
Part Set D
(Not visible in a partitioned system.) When a user presses button D the control unit
sets only those zones where Part Set D attribute = "Yes".
You can apply this attribute to the following zone types: Normal Alarm, Final Exit and
Entry Route.
Installer Menu Options
Page 51