Eaton i-on series Engineering Manual page 80

Hide thumbs Also See for i-on series:
Table of Contents

Advertisement

Installer Menu Options
Type:
(nn=shortcut)
Siren (21)
Strobe (22)
Entry Exit Follow
(23)
Armed (24)
PIR Set Latch (25)
30 40 50
160
Shock Sensor
Reset (26)
30 40 50
160
Walk Test (27)
Page 70
Active when:
The control unit starts a full alarm, a hold up alarm
or a fire alarm (the siren has a distinctive tone during
a fire alarm). The control unit deactivates this output
at the end of the siren time. See page 81 to choose
the siren duration.
a) The control unit starts a Full alarm, hold up alarm
or fire alarm. The output remains active until the
user disarms the system.
b) Setting or unsetting, if you have selected "strobe
on set" and/or "strobe on unset", see page 82.
The entry or exit time starts and deactivates at the
end of the entry/exit time, or if the entry/exit time is
terminated. The output can be used for a separate
entry/exit buzzer. Note that the output does not
operate if the exit mode is silent set or instant set.
The system (or partition) is full or part set.
The system or partition is set. Inactive when the
system or partition is unset or an alarm condition
occurs. The output is active for one second when a
reset is performed or when the control unit leaves
installer mode.
Note: By default this output is at +12V when active
and 0V when inactive. Use the Inverted
attribute if you wish to change this behaviour.
Exit time starts. The output remains active for five
seconds. Use this output to reset shock sensors (for
example, the "Viper").
A user starts Installer- or User Walk Tests. Also
active during the time between silencing and
resetting the system. This output can be used on
movement detectors that are able to switch off the
Walk Test lamp in any state other than a Walk Test.
i-on Range
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
No
Yes