i-on Range
Notes:
1. Appears only if Exit Mode is "Final Door", "Lock Set" or "Exit Terminate".
2. Appears only if Exit Mode is "Timed Set" or "Silent Set".
3. Not available on i-on16, i-on40 or i-on30EX.
4. i-on160EX can have up to 20 partitions, i-on50EX up to five, i-on30EX and i-on40
up to 4.
Notes for Part Set Options
In a Part Setting System, for Part Set B to work you must have at least one zone
with the attribute Part Set B = "Yes", see page 50
In the same way, for Part Set C to work you must have at least one zone with the
attribute Part Set C = "Yes". For Part Set D to work you must have at least one zone
with the attribute Part Set D = "Yes".
In a Partitioned System, for part set to work within a partition you must assign the
"Part Set" attribute to at least one zone belonging to the partition.

Options

Note: The default settings for these options are compliant with EN50131, see page 33.
Changes to some of the defaults may render the system non-compliant.
Name
Use this option to give the Full Set, Part Set, or Partition a name. The control unit
displays this name to the user during setting.
Exit Mode/Part Set Exit Mode
The exit modes available are:
Timed Set
Final Door Set
Use this option to make the system set after a delay.
Use the Exit Time menu (see page 80) to choose the
delay. The control unit logs the start of timed exit.
Note: This option does not comply with BS8243:2010.
Use this option to complete setting the system by
closing a door fitted with a Final Exit zone detector.
Once the door closes the system sets after the Settle
Time expires. Note that the exit time is infinite in this
option.
The control unit logs the start of final door exit.
Notes 1: If you wish to use Final Door Set exit mode
when part setting then:
a) Make sure that you include a zone with the
Final Exit type as one of the part set zones.
b) Make sure you select "Final Door" in Part Set
Final Exit As (see page 81).
2: If you wish to use Final Door Set exit mode
for a Partition then make sure you include a
zone with the type Final Exit in the Partition.
3: Do not try to make a PIR zone act as a Final
Exit. Radio PIR detectors have a "lock out"
period after each activation in order to conserve
battery power. When you set (or part set) the
system a PIR may still be in lockout, during
which it cannot send a signal to complete the
setting process.