2-24 System level recovery procedures
Performing a cold restart
4
At the CM reset terminal for the ACTIVE CPU
5
At the CM reset terminal for the INACTIVE CPU
6
7
8
297-8021-545 Standard 14.02 May 2001
(continued)
WARNING: This action will result in a CALL PROCESSING
OUTAGE.
Please confirm ("YES", "Y", "NO", or "N"):
To confirm the command, type
>YES
and press the Enter key.
Monitor the CM reset terminal for the active central processing unit (CPU) to
determine if the switch restarted.
Note: When the switch restarts, alphanumeric addresses appear in the
status bar for the reset terminal. When the switch restarts, A1 flashes in
the status bar.
If A1
flashes
does not flash after 5 min
Check the status bar for the reset terminal to determine if the CPUs are in
sync.
Note: The word Sync in the status bar indicates that the CPUs are in sync.
The word NoSync indicates that the CPUs are not in sync.
If the CPUs
are in sync
are not in sync
To jam the inactive CPU, type
>\JAM
and press the Enter key.
RTIF response:
Please confirm: (YES/NO)
To confirm the command, type
>YES
and press the Enter key.
RTIF response:
JAM DONE
Do
step 16
step 30
Do
step 7
step 12