Recovering from a dead system in a SuperNode SE switch
48
49
At the IOD frame
50
51
52
53
At the operator MAP terminal
54
and press the Enter key.
where
slm_no
is the number of the SLM (0 or 1) that contains the most recent
image file
Example input:
>BOOT
SLM 0
RTIF response:
Please confirm: (YES/NO)
To confirm the command, type
>YES
and press the Enter key.
RTIF response:
JAM DONE
Wait until A1 flashes on the RESET terminal for the active CPU. Determine
if the switch booted.
If A1
flashes
does not flash after 15 min
Turn on the power converters on input/output controller (IOC) 0.
Note: The vintage of IOC determines if the IOC has one or two power
converters.
Press the RESET button on one of the IOC power converters. While you
press the RESET button, lift the circuit breaker switch for the frame
supervisory panel (FSP) for IOC 0.
Release the RESET button.
Turn on the power inverter that supplies the operator MAP terminal.
Determine if you must log in.
Note: The message Please Login means that you must log in. Your office
parameters determine if the system can log you in automatically.
Example of a MAP response:
Please Login.
If
you must log in
DMS-100 Family NA100 Recovery Procedures LET0015 and up
System level recovery procedures
Do
step 50
step 193
Do
step 55
2-95
(continued)