Restoring the remote oscillator shelf to duplex operation

Application
Use this procedure to restore the remote oscillator shelf (ROS) to duplex
operation. Perform this procedure to conserve emergency power after you
power down one plane of the ROS.
This procedure assumes that you follow the Emergency power
conservation—Shutdown in this document to remove equipment from service.
Equipment must be in normal in-service operation before the need to perform
the procedure for emergency power conservation arises.
Action
The following flowchart provides a summary of the procedure. Use the
instructions in the step-action procedure that follow the flowchart to perform
the recovery task.
Emergency power conservation recovery procedures 5-65
Emergency power conservation
DMS-100 Family NA100 Recovery Procedures LET0015 and up