Restoring the remote oscillator shelf to duplex operation
Restoring the remote oscillator shelf to duplex operation
At the ROS
1
Power up the half of the remote oscillator shelf that you powered down to
conserve emergency backup power.
Note: Slots 1 to 13 associate with message switch (MS) 0. Slots 14 to 26
associate with MS 1.
2
Restore service to the MS that associates with the half of the remote oscillator
shelf that you powered up in step 1. Perform the procedure Restoring the MS
to duplex operation in this document to restore service to the MS.
Emergency power conservation recovery procedures
Emergency power conservation
CAUTION
Potential service interruption or extended outage
Nortel recommends that you contact the Emergency
Technical Assistance Service (ETAS) or the next level of
support before you perform this procedure.
CAUTION
Potential loss of service or extended outage
Use this procedure to conserve emergency backup power.
Do not use this procedure or sections of this procedure for
equipment maintenance purposes.
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap
grounding point of a frame supervisory panel (FSP) to
handle circuit cards. The wrist strap protects the cards
against static electricity damage.
DMS-100 Family NA100 Recovery Procedures LET0015 and up
5-67
(end)