5-180 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one unit of MSB7s
Emergency shutdown of one unit of MSB7s
At the MAP terminal
1
2
3
297-8021-545 Standard 14.02 May 2001
WARNING
Potential service interruption or extended outage
Nortel recommends that you contact the
Emergency-Technical Assistance Services (ETAS) or the
next level of support before you perform this procedure.
WARNING
Potential loss of service or extended outage
Perform this procedure to conserve emergency backup
power. Do not use this procedure or sections of this
procedure for equipment maintenance purposes.
To access the PM level of the MAP display, type
>MAPCI;MTC;PM
and press the Enter key.
To post the PM for the unit that you will power down, type
>POST
MSB7
pm_no
and press the Enter key.
where
pm_no
is the PM identification number (0 to 999)
Example of a MAP response:
MSB7
0 InSv
Links_OOS: CSide
Unit0:
Act
Unit1:
Inact
Determine from the MAP display if the MSB7 unit that you will power down is
the active (Act) or inactive (Inact) unit.
If the unit
is active
is inactive
(continued)
0 , PSide
InSv
InSv
Do
step 4
step 8
0