Nortel DMS-100 Manual page 465

Hide thumbs Also See for DMS-100:
Table of Contents

Advertisement

5-114 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one enhanced network plane
Emergency shutdown of one enhanced network plane
At the MAP terminal
1
2
3
4
297-8021-545 Standard 14.02 May 2001
WARNING
Potential service interruption or extended outage
Nortel recommends that you contact the Emergency
Assistance Service (ETAS) or the next level of support before
you perform this procedure.
WARNING
Potential loss of service or extended outage
Use this procedure to conserve emergency backup power. Do
not use this procedure or sections of this procedure for
equipment maintenance purposes.
To access the Network level of the MAP display, type
>MAPCI;MTC;NET
and press the Enter key.
Example of a MAP display
ENET
System
Plane 0 CSLink
Plane 1 CSLink
Select a plane to remove from service. Note the plane number.
To deload the plane you selected in step 2, type
>DELOAD
plane_no
and press the Enter key.
where
plane_no
is the network plane number (0 or 1)
Example of a MAP response
Request to SET DELOAD ENET Plane:0 submitted.
Request to SET DELOAD ENET Plane:0 passed.
Allow 30 min for traffic to clear on the plane shelf. To monitor the deload
status of the plane shelf, type
>DELOAD
plane_no
Matrix
Shelf 0 1 2 3
.
F – – –
.
F – – –
SET
QUERY
(continued)

Advertisement

Table of Contents
loading