5-56 Emergency power conservation recovery procedures
Emergency power conservation
Restoring the MS to duplex operation
At the MAP terminal
3
4
5
6
297-8021-545 Standard 14.02 May 2001
To access the MS level of the MAP display, type
>MAPCI;MTC;MS
and press the Enter key.
To reload the latest MS image file, type
>LOADMS
ms_number
and press the Enter key.
where
ms_number
is the number of the manual busy MS (0 or 1)
Example of a MAP response:
Request to Load MS: 0 submitted.
Request to Load MS: 0 passed.
Loading completed, entry point is #06045FCO
To perform an out-of-service test on the manual busy MS, type
>TST
ms_number
and press the Enter key.
where
ms_number
is the number of the manual busy MS (0 or 1)
Example of a MAP response:
Request to TEST OOS MS: 0 submitted.
Request to TEST OOS MS: 0 passed.
No node faults were found on MS 0.
No cards were found to be faulty on MS0.
Request to TEST VIA MATE MS: 0 submitted.
Request to TEST VIA MATE MS: 0 passed.
No node faults were found on MS 0.
No cards were found to be faulty on MS 0.
To return the manual busy MS to service, type
>RTS
ms_number
and press the Enter key.
where
ms_number
is the number of the manual busy MS (0 or 1)
Example of a MAP response:
(continued)