5-142 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one LIM unit on each ELPP
At the ELPP
10
11
297-8021-545 Standard 14.02 May 2001
WARNING
Static electricity damage
Wear a wrist strap that connects to a wrist-strap grounding
point on the frame supervisory panel (FSP) or the modular
supervisory panel (MSP) to handle circuit cards. The wrist
strap protects the cards against static electricity damage.
Press down and release the power switch on the faceplate of the NT9X30 and
NT9X31 power converters. Slot 4 for LIM unit 0 and slot 36 for LIM unit 1
contain the NT9X30 power converter. Slot 1 for LIM unit 0 and slot 33 for LIM
unit1 contain the NT9X31 power converter. This procedure powers down the
LIM unit busied in step 9.
Note: The CONVERTER OFF LED goes on when you power down the
NT9X30 or NT9X31 power converter. Ensure that both the NT9X30 and
NT9X31 power converters for the LIM unit busied in step 9 are powered
down.
Return to the procedure Emergency power conservation—Shutdown in this
document and proceed as directed.
(end)