5-116 Emergency power conservation recovery procedures
Emergency power conservation
Emergency shutdown of one enhanced network plane
11
12
13
14
297-8021-545 Standard 14.02 May 2001
and press the Enter key
where
plane_no
is the network plane number (0 or 1)
shelf_no
is the network shelf number (0 to 7)
Example of a MAP display
Request to MAN BUSY ENET Plane:0 Shelf:00 submitted.
Request to MAN BUSY ENET Plane:0 Shelf:00 passed.
To offline the plane shelf, type
>OFFL
plane_no
and press the Enter key
where
plane_no
is the network plane number (0 or 1)
shelf_no
is the network shelf number (0 to 7)
Example of a MAP response
Request to OFFL ENET Plane:0 Shelf:00 submitted.
Request to OFFL ENET Plane:0 Shelf:00 passed.
To access the Shelf level for the ENET shelf you want to remove from service,
type
>SHELF
shelf_no
and press the Enter key
where
shelf_no
is the network shelf number (0 to 7)
To manually busy all the cards on the shelf, type
>BSY
shelf_no
and press the Enter key
where
shelf_no
is the network shelf number (0 to 7)
To offline all the cards on the plane, type
>OFFL
shelf_no
and press the Enter key
where
shelf_no
ALL
ALL
(continued)