Nortel DMS-100 Manual page 374

Hide thumbs Also See for DMS-100:
Table of Contents

Advertisement

Restoring the junctored network to duplex operation
Restoring the junctored network to duplex operation
At the JNET shelf
1
Determine if the power converter is an NT2X70AE card.
If the power converter
is an NT2X70AE card
is not an NT2X70AE card
2
Determine if the frame supervisory panel (FSP) or modular supervisory panel
(MSP) has circuit breakers.
If the FSP or MSP
has circuit breakers
does not have circuit breakers
3
Power up the converter as follows:
Emergency power conservation recovery procedures
Emergency power conservation
WARNING
Potential extended equipment outage
Nortel recommends that you contact the Emergency
Technical Assistance Services (ETAS) to expedite recovery
of equipment.
WARNING
Potential loss of service or extended outage
This procedure restores normal operation after you
performed the emergency power conservation measures. Do
not use this procedure or sections of this procedure for
equipment maintenance purposes.
WARNING
Static electricity damage
Wear a wrist strap that connects to the wrist-strap grounding
point of a frame supervisory panel (FSP) or a modular
supervisory panel (MSP) to handle circuit cards. The wrist
strap protects the cards against static electricity damage.
DMS-100 Family NA100 Recovery Procedures LET0015 and up
Do
step 2
step 5
Do
step 3
step 4
5-25