Commissioning
5.4 Quick commissioning
5.4.2.4

Carrying out quick commissioning

Procedure
Select motor control mode.
Select the I/O configuration to pre-assign the converter interfaces.
• Set the applicable motor standard and the converter supply voltage.
• Select the application for the drive:
– [0] Load cycle with high overload: for applications requiring a high dynamic
– [1] Load cycle with low overload: for applications that do not require a high dynamic
• Set the pulse frequency for the converter.
If an external braking resistor is installed, you must set the maximum permissible braking
power of the braking resistor.
The geared motor of the G115D Motor Mounted drive has been parameterized before factory
delivery.
• Configure your motor in either of the following ways:
– Enter the motor data according to the rating plate of your motor.
– If you use a Siemens motor, select a motor based on its article number. In this case, the
• Set the motor connection (star/delta) and the 87 Hz characteristic.
• Select the temperature sensor for monitoring of the motor temperature.
• Select to reverse the output phase sequence or not.
Define whether the converter actuates a motor holding brake.
94
Motor control (Page 228)
Factory interface setting (Page 73)
performance, e.g. conveyor systems.
performance, e.g. pumps or fans.
values of the selected motor are taken as default motor data.
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive