Advanced commissioning
6.10 Motor holding brake
7. If the load sags after switching on the motor, then you must increase the motor torque
when opening the motor holding brake. Depending on the control mode, you must set
different parameters:
– U/f control (p1300 = 0 to 3):
– Vector control (p1300 ≥ 20):
8. Switch off the motor.
9. Check the behavior of the drive immediately after the motor has been switched off:
– If the motor holding brake closes too late, the load briefly sags before the motor
– If the motor waits too long before switching off after the motor holding brake has
You have commissioned the motor holding brake function.
Parameters
Basic settings
Parameter
p1215
p1216
p1217
r0052.12
182
For applications involving a pulling load, e.g. lifting gear/crane, if p1216 is too long,
then the load can briefly sag/sink after the motor holding brake is opened. If you
reduce p1216, then the amount that the load sags/sinks is reduced.
Increase p1310 in small steps.
Increase p1351 in small steps.
Increase p1475 in small steps.
holding brake closes.
Set a larger value for p1217.
closed, reduce p1217.
Description
Enable motor holding brake
Motor holding brake opening time
[s]
Motor holding brake closing time
[s]
CO/BO: Status word 1: motor
holding brake open
Setting
0: Motor holding brake locked (factory setting)
1: Motor holding brake just like the sequence
control
2: Motor holding brake permanently open
3: Motor holding brake just like the sequential
control, connected via BICO
p1216 > braking signal relay runtimes + brake
release time
Factory setting: 0.1
p1217 > braking signal relay runtimes + brake
closing time
Factory setting: 0.1
-
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B