Siemens SINAMICS G115D Operating Instructions Manual page 273

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
Parameters
Parameters
r0031
p0311[0...n]
r0333[0...n]
p1080[0...n]
p1082[0...n]
p1300[0...n]
p2165[0...n]
p2168[0...n]
p2181[0...n]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Description
Torque actual value, smoothed
[Nm]
Rated motor speed [rpm]
Rated motor torque [Nm]
Minimum speed [rpm]
Maximum speed [rpm]
Open-loop/closed-loop control
operating mode
Load monitoring blocking moni-
toring threshold, upper [rpm]
Load monitoring blocking moni-
toring torque threshold [Nm]
Load monitoring response
Advanced commissioning
6.24 Monitoring the driven load
Setting
Displays the smoothed torque actual value.
Sets the rated motor speed.
Factory setting: 0
Displays the rated motor torque.
Sets the lowest possible motor speed.
Factory setting: 0
Sets the highest possible speed.
Factory setting: 1500
Sets the open and closed-loop control mode.
0: U/f control with linear characteristic (factory
setting)
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
3: U/f control with parameterizable characteristic
4: U/f control with linear characteristic and ECO
5: U/f control for drives requiring a precise fre-
quency (e.g. textiles)
6: U/f control for drives requiring a precise fre-
quency and FCC
7: U/f control for a parabolic characteristic and
ECO
19: U/f control with independent voltage setpoint
20: Speed control (encoderless)
22: Torque control (encoderless)
Sets the upper speed threshold of the stall moni-
toring of the pump or fan.
Factory setting: 0
Sets the torque threshold of the stall monitoring
of the pump or fan.
Factory setting: 10000000
Sets the response when evaluating the load moni-
toring.
0: Load monitoring disabled (factory setting)
7: Pump/fan load monitoring as alarm (A07891,
A07892, A07893)
8: Pump/fan load monitoring as fault (F07894,
F07895, F07896)
271