3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 ... p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
❒
Parameters
Parameters
r0031
p0311[0...n]
r0333[0...n]
p1080[0...n]
p1082[0...n]
p1300[0...n]
p2165[0...n]
p2168[0...n]
p2181[0...n]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Description
Torque actual value, smoothed
[Nm]
Rated motor speed [rpm]
Rated motor torque [Nm]
Minimum speed [rpm]
Maximum speed [rpm]
Open-loop/closed-loop control
operating mode
Load monitoring blocking moni-
toring threshold, upper [rpm]
Load monitoring blocking moni-
toring torque threshold [Nm]
Load monitoring response
Advanced commissioning
6.24 Monitoring the driven load
Setting
Displays the smoothed torque actual value.
Sets the rated motor speed.
Factory setting: 0
Displays the rated motor torque.
Sets the lowest possible motor speed.
Factory setting: 0
Sets the highest possible speed.
Factory setting: 1500
Sets the open and closed-loop control mode.
0: U/f control with linear characteristic (factory
setting)
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
3: U/f control with parameterizable characteristic
4: U/f control with linear characteristic and ECO
5: U/f control for drives requiring a precise fre-
quency (e.g. textiles)
6: U/f control for drives requiring a precise fre-
quency and FCC
7: U/f control for a parabolic characteristic and
ECO
19: U/f control with independent voltage setpoint
20: Speed control (encoderless)
22: Torque control (encoderless)
Sets the upper speed threshold of the stall moni-
toring of the pump or fan.
Factory setting: 0
Sets the torque threshold of the stall monitoring
of the pump or fan.
Factory setting: 10000000
Sets the response when evaluating the load moni-
toring.
0: Load monitoring disabled (factory setting)
7: Pump/fan load monitoring as alarm (A07891,
A07892, A07893)
8: Pump/fan load monitoring as fault (F07894,
F07895, F07896)
271