Protocols Used - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Wiring
4.13 Connecting to PROFINET and Ethernet
4.13.3

Protocols used

The converter supports the protocols listed in the following tables. The address parameters,
the relevant communication layer as well as the communication role and the communication
direction are specified for each protocol.
You require this information to set the appropriate safety measures to protect the automation
system, e.g. in the firewall.
As the security measures are limited to Ethernet and PROFINET networks, no PROFIBUS
protocols are listed in the table.
Table 4- 1
PROFINET protocols
Protocol
Port
number
DCP:
Not
relevant
Discovery and
configuration
protocol
LLDP:
Not
relevant
Link Layer Dis-
covery Protocol
MRP:
Not
relevant
Media Redun-
dancy Protocol
PTCP
Not
relevant
Precision
Transparent
Clock Protocol
PROFINET IO
Not
data
relevant
PROFINET Con-
34964
text Manager
76
Layer
Function/description
(2) Link layer
(4) Transport layer
Accessible stations, PROFINET Discovery and configuration
(2) Ethernet II and
IEEE 802.1Q and
DCP is used by PROFINET to determine PROFINET devices and to make
Ethertype 0x8892
basic settings.
(PROFINET)
DCP uses the special multicast MAC address:
xx-xx-xx-01-0E-CF,
xx-xx-xx = Organizationally Unique Identifier
(2) Ethernet II and
PROFINET Link Layer Discovery protocol
IEEE 802.1Q and
LLDP is used by PROFINET to determine and manage neighborhood
Ethertype 0x88CC
relationships between PROFINET devices.
(PROFINET)
LLDP uses the special multicast MAC address:
01-80-C2-00-00-0E
(2) Ethernet II and
PROFINET medium redundancy
IEEE 802.1Q and
MRP enables the control of redundant routes through a ring topolo-
Ethertype 0x88E3
gy.
(PROFINET)
MRP uses the special multicast MAC address:
xx-xx-xx-01-15-4E,
xx-xx-xx = Organizationally Unique Identifier
PROFINET send clock and time synchronization, based on IEEE
(2) Ethernet II and
1588
IEEE 802.1Q and
Ethertype 0x8892
PTC is used to implement send clock synchronization and time syn-
(PROFINET)
chronization between RJ45 ports, which are required for IRT opera-
tion.
PTCP uses the special multicast MAC address:
xx-xx-xx-01-0E-CF,
xx-xx-xx = Organizationally Unique Identifier
PROFINET Cyclic IO data transfer
(2) Ethernet II and
IEEE 802.1Q and
The PROFINET IO telegrams are used to transfer IO data cyclically
Ethertype 0x8892
between the PROFINET IO controller and IO devices via Ethernet.
(PROFINET)
PROFINET connection less RPC
(4) UDP
The PROFINET context manager provides an endpoint mapper in
order to establish an application relationship (PROFINET AR).
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive

Advertisement

Table of Contents
loading

Table of Contents