Motor Mounted
Figure 11-6
Motor
Minimum clearance of motor with G115D from wall for air intake
Motor Mounted
FSA
Without brake
x [mm]
71
54
80
28
90
21
100
-
112
-
132
-
NOTICE
Collision of mounted components on the converter
With a projecting converter on Motor Mounted, care should be taken to avoid potential
collisions between the mounted components on the converter (connectors, cable entries
etc.) and neighboring components.
See mounting clearance of the converter (150 mm) in section Mounting the G115D Motor
Mounted drive (Page 35).
The permissible coolant temperature (ambient temperature at installation location) is
‑15 °C to +40 °C as standard for an installation altitude of up to 1000 m above sea level.
Deviating data are specified on the rating plate.
When mounting in the vertical position with the fan cover facing upward, provide protection
to prevent foreign objects falling in, e.g. using an appropriate cover.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Minimum clearance of motor with G115D from wall for air intake
With brake
x [mm]
15
20
20
-
-
-
Additional information on the SIMOGEAR geared motor
Wall Mounted
FSB
Without brake
With brake
x [mm]
x [mm]
-
-
-
-
29
20
22
20
25
25
30
30
11.2 Specific data motor
Wall Mounted
15
20
20
20
25
30
377