Derating Data; Current Derating As A Function Of The Installation Altitude; Current Derating As A Function Of The Line Voltage - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

10.1.6

Derating data

10.1.6.1

Current derating as a function of the installation altitude

The permissible converter output current is reduced above an installation altitude of 1000 m.
10.1.6.2

Current derating as a function of the line voltage

The converter operates at 100% rated output current at a line voltage from 380 V to 480 V.
The permissible converter output current is reduced linearly when the line voltage is above
480 V.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
10.1 Technical data of the G115D converter with SIMOGEAR geared motor
Technical data
337