Advanced commissioning
6.14 Setpoints
Table 6- 24
Number
p1030[0...n]
p1037[0...n]
p1038[0...n]
p1043[0...n]
p1044[0...n]
206
Advanced settings
Name
Motorized potentiometer configu-
ration
Motorized potentiometer, maxi-
mum speed [rpm]
Motorized potentiometer, mini-
mum speed [rpm]
BI: Motorized potentiometer,
accept setting value
CI: Motorized potentiometer,
setting value
Factory setting
Configuration for the motorized potentiometer
Factory setting: 00110 bin
.00
Storage active
= 0: After the motor has been switched on, the
setpoint = p1040
= 1: After the motor has switched off, the con-
verter saves the setpoint.
After the motor has switched on, the setpoint =
the stored value.
.01
Automatic mode, ramp-function generator active
(1-signal via BI: p1041)
= 0: Ramp-up/ramp-down time = 0
= 1: With ramp-function generator
In manual mode (p1041 = 0), the ramp-function
generator is always active.
.02
Initial rounding active
1: With initial rounding. Using the initial rounding
function it is possible to enter very small setpoint
changes.
.03
Storage in NVRAM active
1: If bit 00 = 1, the setpoint is retained during a
power failure.
.04
Ramp-function generator always active
1: The converter also calculates the ramp-function
generator when the motor is switched off.
The converter limits the motorized potentiometer
output to p1037.
Factory setting: 0 rpm
After quick commissioning, the converter sets the
parameter to the appropriate value.
The converter limits the motorized potentiometer
output to p1038.
Factory setting: 0 rpm
After quick commissioning, the converter sets the
parameter to the appropriate value.
Signal source for accepting the setting value. The
motorized potentiometer accepts the setting
value p1044 on signal change p1043 = 0 → 1.
Factory setting: 0
Signal source for the setting value
Factory setting: 0