Appendix
A.2 Acceptance tests for the safety functions
3.
4.
You have performed the acceptance test of the STO function.
506
Select STO
3.1.
Select STO while the motor is running.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2.
Check the following:
When controlled via
PROFIsafe
The converter signals
the following:
"STO selection via
PROFIsafe"
(r9772.20 = 1)
If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it remains
at standstill.
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
The converter signals the following:
"STO is selected" (r9773.0 = 1).
"STO is active" (r9773.1 = 1).
Deselect STO
4.1.
Deselect STO.
4.2.
Check the following:
STO is not active (r9773.1 = 0).
The converter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
When controlled via fail-
safe digital inputs (F-DI)
The converter signals
the following:
"STO Selection via
terminal"
(r9772.17 = 1)
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
When controlled via
terminals STO_A and
STO_B on Power Mod-
ule
The converter sig-
nals the following:
"STO Selection via
terminal on Power
Module"
(r9772.25 = 1)
SINAMICS G115D distributed drive