Function description
Overload response for p0290 = 0
The converter responds depending on the control mode that has been set:
• In vector control, the converter reduces the output current.
• In U/f control, the converter reduces the speed.
Once the overload condition has been removed, the converter re-enables the output current
or speed.
If the measure cannot prevent a converter thermal overload, then the converter switches off
the motor with fault F30024.
Overload response for p0290 = 1
The converter immediately switches off the motor with fault F30024.
Overload response for p0290 = 2
We recommend this setting for drives with square-law torque characteristic, e.g. fans.
The converter responds in 2 stages:
1. If you operate the converter with increased pulse frequency setpoint p1800, then the
converter reduces its pulse frequency starting at p1800.
In spite of the temporarily reduced pulse frequency, the base-load output current remains
unchanged at the value that is assigned to parameter p1800.
Once the overload condition has been removed, the converter increases the pulse
frequency back to the pulse frequency setpoint p1800.
2. If it is not possible to temporarily reduce the pulse frequency, or the risk of thermal overload
cannot be prevented, then stage 2 follows:
– In vector control, the converter reduces its output current.
– In U/f control, the converter reduces the speed.
Once the overload condition has been removed, the converter re-enables the output
current or speed.
If both measures cannot prevent a power unit thermal overload, then the converter switches
off the motor with fault F30024.
Overload response for p0290 = 3
If you operate the converter with increased pulse frequency, then the converter reduces its
pulse frequency starting at the pulse frequency setpoint p1800.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
6.20 Converter protection using temperature monitoring
Advanced commissioning
257