Number
r2294
p2295
p2296[0...n]
p2297[0...n]
p2298[0...n]
p2299[0...n]
p2302
Adapting the actual value of the technology controller
Parameter
p2264[0...n]
p2265
p2266
p2267
p2268
p2269
p2270
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Name
CO: Technology controller output
signal [%]
CO: Technology controller output
scaling [%]
CI: Technology controller output
scaling
CI: Technology controller maxi-
mum limiting signal source
CI: Technology controller mini-
mum limiting signal source
CI: Technology controller limita-
tion offset
Technology controller output
signal start value [%]
Description
CI: Technology controller actual
value
Technology controller actual value
filter time constant [s]
CO: Technology controller actual
value after filter [%]
Technology controller upper limit
actual value [%]
Technology controller lower limit
actual value [%]
Technology controller gain actual
value [%]
Technology controller actual value
function
Advanced commissioning
6.16 PID technology controller
Factory setting
Display and connector output for the output sig-
nal of the technology controller.
Sets the scaling for the output signal of the tech-
nology controller.
Factory setting: 100
Sets the signal source for the scaling value of the
technology controller.
Factory setting: 2295
Sets the signal source for the maximum limiting
of the technology controller.
Factory setting: 1084
Sets the signal source for the minimum limiting of
the technology controller.
Factory setting: 1087
Sets the signal source for the offset of the output
limiting of the technology controller.
Factory setting: 0
Sets the start value for the output of the technol-
ogy controller.
Factory setting: 0
Setting
Sets the signal source for the actual value of the
technology controller.
Factory setting: 0
Sets the time constant for the actual value filter
(PT1) of the technology controller.
Factory setting: 0
Display and connector output for the smoothed
actual value after the filter (PT1) of the technolo-
gy controller.
Sets the upper limit for the actual value signal of
the technology controller.
Factory setting: 100
Sets the lower limit for the actual value signal of
the technology controller.
Factory setting: -100
Sets the scaling factor for the actual value of the
technology controller.
Factory setting: 100
Setting to use an arithmetic function for the actu-
al value signal of the technology controller.
0: Output (y) = input (x) (factory setting)
1: Root function (root from x)
2: Square function (x * x)
3: Cube function (x * x * x)