6.15.2
Invert setpoint
Function description
The function inverts the sign of the setpoint using a binary signal.
Example
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary
signal of your choice.
Table 6- 25
Parameter
p1113 = 722.1
p1113 = 2090.11
Parameters
Parameter
p1113[0...n]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Application examples showing how a setpoint is inverted
Description
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Converter inverts the setpoint.
Inverts the setpoint via the fieldbus (control word 1, bit 11).
Description
BI: Setpoint inversion
Advanced commissioning
6.15 Setpoint processing
Setting
Sets the signal source to invert the setpoint.
Factory setting: dependent upon the converter
211