Flow characteristic
To set the characteristic, you require the following data from the machine manufacturer for
each speed interpolation point:
• The flow rate of the fluid-flow machine associated with the 5 selected converter speeds
• At constant speed, the power drawn which is associated with the 5 flow rates corresponds
to the line frequency and mechanical throttling of the flow rate.
Parameters
Parameter
r0039[0...2]
p0040
r0041
r0042[0...2]
p0043
p3320[0...n]
p3321[0...n]
p3322[0...n]
p3323[0...n]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
6.26 Calculating the energy saving for fluid flow machines
Description
CO: Energy display [kWh]
Reset energy consumption display Setting p0040 = 1 to reset the display in r0039
Energy saved [kWh]
CO: Process energy display [Wh]
BI: Energy consumption display
enabled
Fluid flow machine power, point 1
[%]
Fluid flow machine speed, point 1
[%]
Fluid flow machine power, point 2
[%]
Fluid flow machine speed, point 2
[%]
Advanced commissioning
Setting
[0] Energy consumption since the last reset.
[1] Energy drawn since the last reset.
[2] Energy fed back since the last reset.
r0039 serves as reference signal of r0042.
and r0041.
Factory setting: 0
Displays the saved energy referred to 100 operat-
ing hours. For an operating time of below 100
hours, the display is interpolated up to 100 hours.
[0] Energy consumption since the last reset.
[1] Energy drawn since the last reset.
[2] Energy fed back since the last reset.
For display as process variable. Enable with
p0043.
Sets the signal source (BI: p0043 = 1 signal) to
enable/reset the process energy display in r0042.
Factory setting: 0
Specifies the power (P) of point 1 as a [%].
Factory setting: 25
Specifies the speed (n) of point 1 as a [%].
Factory setting: 0
Specifies the power (P) of point 2 as a [%].
Factory setting: 50
Specifies the speed (n) of point 2 as a [%].
Factory setting: 25
277