Alarms, faults and system messages
8.4 Alarms, alarm buffer, and alarm history
Parameters
Parameters of the alarm buffer and the alarm history
Parameter
p2111
r2122[0 ... 63]
r2123[0 ... 63]
r2124[0 ... 63]
r2125[0 ... 63]
r2132
r2134[0 ... 63]
r2145[0 ... 63]
r2146[0 ... 63]
Extended settings for alarms
Parameter
You can change up to 20 different alarms into faults or suppress alarms:
p2118[0 ... 19]
p2119[0 ... 19]
For more information about this function, see function diagram 8075 and parameter
description in the List Manual.
304
Description
Alarm counter
Alarm code
Alarm time received in milli-
seconds
Alarm value
Alarm time removed in milli-
seconds
CO: Actual alarm code
Alarm value for float values
Alarm time received in days
Alarm time removed in days
Description
Changing message type,
message number
Changing message type,
type
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Setting
Number of alarms that have occurred after the
last reset.
When setting p2111 = 0, the following is initiat-
ed:
All of the alarms that have been removed
from the alarm buffer [0...7] are transferred
into the alarm history [8...63].
The alarm buffer [0...7] is deleted.
Factory setting: 0
Displays the numbers of the alarms that have
occurred.
Displays the time in milliseconds when the alarm
occurred.
Displays additional information about the alarm.
Displays the time in milliseconds when the alarm
was removed.
Displays the code of the alarm that last occurred.
Displays additional information about the alarm
that occurred for float values.
Displays the time in days when the alarm oc-
curred.
Displays the time in days when the alarm was
removed.
Setting
Selects faults or alarms for which the message
type should be changed.
Factory setting: 0
Sets the message type for the selected fault or
alarm.
1: Fault
2: Alarm
3: No message
Factory setting: 1