4.6

Forming DC link capacitors

Introduction
You have to reform the DC link capacitors if the converter/Electronic Module has been stored
for more than one year. Non-formed DC link capacitors can damage the converter in
operation.
Precondition
The converter/Electronic Module has not yet been used, and according to the production date
it was made over a year ago.
The production date is coded in the 3rd and 4th digit of the serial number. You may find the
serial number easily on the service information label at the front of the Electronic Module.
Production year and month
• Example: Serial number S XAM002-002137 → Production date October 2020
Function description
Procedure
You form the DC link capacitors by supplying the converter with a line voltage of ≤ 100% of
the rated voltage for a defined time.
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Digit ③
Production year
M
2020
N
2021
P
2022
R
2023
...
Digit ④
1 ... 9
...
4.6 Forming DC link capacitors
Production month
January ... September
0
October
N
November
D
December
Wiring
51