Siemens SINAMICS G115D Operating Instructions Manual page 130

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
6.6 Drive control via Ethernet/IP
4. Select the Ethernet/IP profile:
5. Switch off the converter power supply.
6. Wait until all LEDs on the converter are dark.
7. Switch on the converter power supply again.
You have now configured the converter for communication via Ethernet/IP.
Parameters
Parameter
p2030
p8920
p8921
p8922
p8923
p8925
r8931
r8932
r8933
p8980
128
SINAMICS profile
p8980 = 0
Use p0922 to select the appro-
priate telegram.
Telegrams (Page 113)
Description
Field bus interface protocol selec-
tion
PN Name of Station
PN IP Address
PN Default Gateway
PN Subnet Mask
Activate PN interface configura-
tion
PN IP Address actual
PN Default Gateway actual
PN Subnet Mask actual
Ethernet/IP profile
ODVA AC/DC drive profile
p8980 = 1
p0922 = 1: The converter communicates via telegram 1. Other
telegrams are not possible. If necessary, however, you can ex-
tend the telegram 1.
Expanding or freely interconnecting telegrams (Page 125)
If necessary, set the following parameters:
p8981
p8982
p8983
Setting
0: No protocol
7: PROFINET
10: Ethernet/IP
The default setting is dependent upon the con-
verter.
Sets the station name for the onboard PROFINET
interface.
Sets the IP address for the onboard PROFINET
interface.
Factory setting: 0
Sets the default gateway for the onboard
PROFINET interface.
Factory setting: 0
Sets the subnet mask for the onboard PROFINET
interface.
Factory setting: 0
Setting to activate the interface configuration
0: No function (factory setting)
2: Activate and save configuration
3: Delete configuration
Displays the actual IP address.
Displays the actual default gateway.
Displays the actual subnet mask.
Sets the profile for Ethernet/IP.
0: SINAMICS
1: ODVA AC/DC
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive