Corrective maintenance
9.4 Firmware upgrade and downgrade
10.Switch on the converter power supply again.
If the firmware downgrade was successful, after several seconds the converter LED RDY
turns green.
The converter is reset to factory settings after firmware downgrade.
11. Transfer the settings from your data backup to the converter.
You have downgraded the converter firmware to an older version and transferred the
settings to the converter.
9.4.4

Correcting an unsuccessful firmware upgrade or downgrade

Precondition
The converter signals an unsuccessful firmware upgrade or downgrade with a quickly
flashing LED RDY and a lit-up LED BF.
Correcting a failed upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
• Have you inserted the card properly?
• Does the card contain the correct firmware?
Repeat the firmware upgrade or downgrade procedure.
328
Memory card → converter (Page 285)
PG/PC → converter (Page 288)
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B